Chapter 32.1 Introduction
Control engineer has 2 main goals:
1. Set point x(t) achievement  by the output signal  y(t).
Ideal is a steady state x(t)=y(t) after a possibly short time with the small oscillations for example.
There are other optimal benchmarks too.
2. Disturbances z(t) suppresion.
Note
Optimal x(t) response doesn’t assure optimal disturbances z(t) suppresion and vice versa.

Chapter 32.2 The set point x(t) and disturbance z(t) influence on the output signal
– The x(t)–>y(t) influence is inclosed in the closed loop transfer function  Gz(s)=y(s)/x(s)
– The z(t)–>y(t) influence is inclosed in the disturbance transfer function Gzakl(s)=y(s)/z(s)

32-1a
Fig. 32-1
Fig. 32-1a The general closed loop system with the disturbance z(t).
Fig. 32-1b The more detailed closed loop system example  with the disturbance z(t). The disturbance acts on the object input here.
I propose a bit of math now. The R(s) is a controller  transfer function for example PID.
32-2a
Fig. 32-2
Note that Gz(s) trannsfer function is the same as a “most important control theory” formula.
32-3
Fig. 32-3
The numerator of the Gzakl(s) disturbance transfer function is other than numerator of the Gz(s) closed loop transfer function.
It’s the reason that optimal PID parameters based on set point x(t) aren’t  optimal based on disturbance zakl(s).
But when  disturbance zakl(s) is in the “middle” as under?
32-4a
Fig. 32-4
Fig. 32-4a is more accurate than general Fig. 32-1a with the “middle” disturbance. Please assume that G1(s) is a controller part and this “controller” transfer function is R(s)*G1(s) and the new “object” is G2(s) now. See at the Gz(s) and Gzakl(s) in the Fig. 32-2 again and the Fig. 32-4b formulas are as clear as day.
Conclusion
The more is the z(t) disturbance “right”  the more distinct is y(t) responce.  You will be convinced in this chapter.

Chapter 32.3 Two-stage heat exchanger
Chapter 32.3.1 Why do we visit the thermal engineering?

Two-stage heat exchanger is a good analysis example for:
– Disturbance analysis
– Different control systems structure –>useful in the next chapter

Chapter 32.3.2 Two-stage heat exchanger as a opened loop
32-5a
Fig. 32-5
The exchanger is intended for control systems analysis, not for thermal engineering teaching. We do very big simplifications then.
1-The liquid doesn’t  steam and freeze.  All temperatures are allowed even +100000ºC or -100000ºC! The last temperature doesn’t exist in the world really but it exists in in this course world.
2-Positive voltage on the immersion resistant heater heats and negative cools! This is so-called Peltier element known from the XIX century.
3-The mixers (not visible in the figure)  are working all the time in the both tanks. It means the momentary  liquid temperature Tc1 is the same in every tank1 place.  The analogical is Tc2 in the tank1. The Tc1 is mostly different than Tc2. These temperature depend on the set pont x(t). The set point x(t) voltage is a input signal to the tank 1, because voltage gain of the power amplifier is ku=1. The heat is transferred from tank1 to tank2 by the aid of coiled tubes and circulating pump.  The momentary liquid temperatures in the 2 coiled tubes  are the same Tc1 . It means that Tc1 is an input signal to tank2. Tc3 is a temperature measured by the thermometer. Tc3 is a little delayed by the inertia of the metalic thermometer case. There is Tc1=Tc2=Tc3 in the steady state.
4– Step type set point x(t)=+10V (corresponding +100 ºC)  will cause after some time the Tc1=+100 ºC  and after some time Tc2=+100 ºC and after some time Tc3=+100 ºC as a +10V on the thermometer.
Note that set point x(t)=+10V caused y(t)=+10V after some time. It’s like a amplifier K=1 with 3 inertia. All this complicated system is replaced by the simple electronic amplifier with inertia! The analysis is much easier now.
Analogically
+5V–>Tc1=Tc2=Tc3=+50ºC–>+5V
0V–>Tc1=Tc2=Tc3=0ºC–>0V
5– Null initial state Tc1=Tc2=Tc3=0ºC
6
– Power amplifier ku=1 (emitter follower for example) ensures constant voltage on the resistant immense heater, regardless of its resistance.
The set point slider is set immediately from low to up position. It’s typical step type x(t)=+100ºC signal.  What are the Tc1, Tc2 and Tc3 signals?
Call Desktop/PID/18_analiza zakłóceń/01_3T.zcos
32-6a
Fig. 32-6
Two-stage heat exchanger model. You don’t see power amplifier because ku=1.
Click “start”
32-7
Fig. 32-7
Tc3 follows Tc2 and Tc2 follows Tc1.
The Tc3 delay is small because thermometer inertia is small.
There is Tc1=Tc2=Tc3=100ºC in steady state.

Chapter 32.3.3 Heat exhanger as a closed loop
Classical PID control system without disturbances.
32-8a
Fig. 32-8
The higher system and the lower model are equivalent.
Call Desktop/PID/18_analiza zakłóceń/02_3T_Kp10_I7_D2.zcos
32-9a
Fig. 32-9
You tested it earlier—>chapter 30 Fig.30-50. But you didn’t know it was a heat exchanger.  The signal y(t)=Tc3 is after  temperature/voltage transformer.  It transforms Tc3 temperature 0…+100 ºC for voltage 0…+10V .
Click “start”
32-10a
Fig. 32-10
You see “cutted” sPID(t)  and not “cutted”  Tc1(t), Tc2(t) (unhappy “fuzzy yellow Tc2(t)) and y(t)=Tc3(t) temperatures on the Fig. 32-10a and all the not cutted Tc1(t), Tc2(t) and Tc3(t) temperatures on the Fig. 32-10b.
 Set point x(t)=+10V –>+100ºC  step type in t=3sec t “wishes” a y(t)=Tc3(t)=+100ºC–>+10V  after some time.

The initial Tc1(t)=Tc2(t)=Tc3(t)=0. The initial controller sPID(t)=210 is very big. Remind please the big initial proportional and especially very  big differential components PID!
Initial sPID(t)=210 “wishes” +21 000ºC in tank no.1 in steady state , more than sun temperature! But after circa 1 sec. it “wishes” to cool the liquid up to -1200ºC! These big sPID(t) changes enables good dinamic. Remember that our system as ideal. There are power limits. The real systems aren’t so ideal and this problem will be analised in chapter 34.

Chapter 32.4 The temperature control of the heat exchanger with the disturbance in different places.
Chapter 32.4.1 Introduction
Return to the formulas in the Fig. 32-4b, especially to the conclusion – “The more is the z(t) disturbance “right”  the more distinct is y(t) responce”.  The next subchapters  confirm it.
The positive disturbance-additonal heater will be given before first, second and third inertia in Fig. 32-8. Finally will be given the most mean disturbance-directly for output y(t) e.i. for thermometer output.

Chapter 32.4.2 Disturbance before first inertia-additional heater by the heater of the tank no. 1.
32-11a
Fig. 32-11
The positive z(t)=+0.4 disturbance is a contact short circuit e.i +4 V on the additional resistance heater next to main heater in the tank no. 1. It causes additional heating. The main and additional heater resistances are equal. E.i. these same voltage steps cause this same temperature liquid increase.
Call Desktop/PID/18_analiza zakłóceń/03_3T_pierwsza_inercja_+zakl.zcos
32-12a
Fig. 32-12
Click “start”
32-13
Fig. 32-13
I remind that y(t)=1 is a +100ºC.
The positive 40% additional heating was compensating by the 40% power decrease. The disturbance is hardly visible.

Chapter 32.4.3 Disturbance before second inertia-additional heater by the  coil tube heater of the tank no. 2.
32-14a
Fig. 32-14
Call Desktop/PID/18_analiza zakłóceń/04_3T_druga_inercja_+zakl.zcos
32-15a
Fig. 32-15
Click “start”
32-16
Fig. 32-16
The x(t) response is the same as before. It’s obviously. But the y(t) suppresion is more rapid now. It confirms the Fig. 32-4b conclusion. The more is the z(t) disturbance “right”  the more distinct is y(t) responce. The  blue sPID(t) controller reaction  is more rapid too.

Chapter 32.4.4 Disturbance before second  inertia-additional heater acts directly for a thermometer
The disturbances acting directly for output or near output are most mean. The resistance wire is is winded on the metalic thermometer case here.
32-17a
Fig. 32-17
There are 2 influences on thermometer
– Liquid temperature Tc2 of the tank no. 2
– “Winded” resistance heater – the z(t)=+4V disturbance
Call Desktop/PID/18_analiza zakłóceń/05_3T_trzecia_inercja_+zakl.zcos


Fig. 32-18
Click “start”
32-19
Fig. 32-19
The system behaviour is similar but more rapid than before. The positive 40% additional heating was compensating by the 40% power decrease and y(t)=Tc3(t) returned to its previous value y(t)=1–>+100ºC. It’ absolutely true but Tc3(t)=+100ºC isn’t a liquid Tc2(t) temperature in steady state! Let’s test Tc2(t) time process.
Call Desktop/PID/18_analiza zakłóceń/06_3T_trzecia_inercja_Tc2_+zakl.zcos
32-20a
Fig. 32-20
We observe Tc2(t) temperature too.
Click”start”
32-21
Fig. 32-21
Note-The Tc2 temperature is a “fuzzy” yellow colour!
The PID, as every moral controller, tries to compensate the disturbance and do x(t)=y(t)=Tc3. And controller succeed  in his job–> y(t)=x(t)! But the themometer value is falsified by additional themometer value. Thermometer “thinks” that is a Tc3=Tc2+40ºC=100ºC but the real liquid temperature is  Tc2=60ºC!

Chapter 32.4.5 The most mean disturbance-Directly on output, after themometer!

32-22a

Fig. 32-22
It seems like a sabotage! Somebody connected to the transmission wire a special device-adder. Controller thinks that the temperature is now y(t)=Tc3+z(t). Remember that PID tries to do steady state x(t)=y(t) so the real temperature will be Tc3=x(t)-z(t).
Call Desktop/PID/18_analiza zakłóceń/07_3T_za_-trzecia_+zakl.zcos
32-23a
Fig. 32-23
This is Fig. 32-22 system Xcos model.
Click “start”
32-24
Fig. 32-24
PID tries to do steady state x(t)=y(t) so the real temperature will be Tc3=x(t)-z(t)=100ºC40ºC=+60ºC. The temperature Tc3-unhappy “fuzzy” yellow colour, confirms it.

Chapter 32.5 The most important disturbance suppresion conclusions

Fig. 32-25
1. The more right is the disturbance the more is distinct
The more “right” is the disturbance z(t)- the “lower” is G2(s). Other words, G2(s) is more similar to proportional unit and  that disturbance transfer function Gzakl(s) has less inertia. The response y(t) is more rapid then. The Fig. 32-13, 16, 19 , 21 and 24 confirm it.

2. The most mean disturbance-directly on output or on controller input
The Fig. 32-21 is an example when disturbance z(t) is near the output and the Fig. 32-24 when disturbance z(t) acts directly on output. This phenomenon is known not only in the control theory. The most mean are the activities directly for a decision-making processes. Do you know   Ken Follet-author  “Eye of the Needle” -World War Two times? The german spy “Needle” informed Hitler that D-day in 1944 will be here and not here.  Hitler made fatal decision in connection with falsified information.  “Needle” was a bad sensor-the analogy is quite visible here.
The disturbance z3(t) acting directly on controller input Fig. 32-25c is mean too. The controller “thinks” that the set point x(t) is changed now.